Print Back

FlexKraft™ Air-Cooled Rectifiers provide premium DC power and performance for demanding industrial environments. Designed for 24/7 continuous operation under harsh conditions, the rectifiers include unique features such as Single and Multiple Outputs with Optional Polarity Reversal, upgradeable power, self-serviceability and fail-safe operation.

With its modular design and an output ranging from 0-120V and 0-30,000A and a multitude of Control Options, we offer the flexibility to provide a best-

more
Unit of Measure

Specifications

Alternating Current (AC) Supply Voltage

480 VAC +/- 10%, 60 Hz, 3 Phase

Electromagnetic Compatibility (EMC) Conformity

According to IEC 61000-6-4, Emissions, and IEC 61000-6-2, Immunity

Low Voltage Directive (LVD) Conformity

According to IEC 50178

Protection Class

IP 32

Power Factor at Rated Load

>0.93

Typical Efficiency at Rated Output

0.90

Maximum Ambient Temperature

104 ºF

Derated Operation Ambient Temperature

up to 122 ºF

Cooling

Forced Air-Cooling

Maximum Relative Humidity

85 %

Control Precision (Voltage/Current)

<+/- 1 %

Direct Current (DC) Ripple

< 1% of rated output current at constant current mode in the entire range of regulation.

Regulation Range

Stepless at constant voltage or current 0-100 %

Duty Ratio

Designed for continuous operation at rated load up to 3300 ft altitude.

Protection

Module Failure Open circuit Over-current Over-temperature Over-voltage Short circuit

Direct Current (DC) Output Voltage

0 to 12 V 0 to 15 V 0 to 24 V 0 to 30 V 0 to 48 V 0 to 60 V

Number of Power Modules

10

Output Current at 0 to 12 Volt Direct Current (DC) Voltage

6000 A

Output Current at 0 to 12 Volt Direct Current (DC) Voltage (Dual Power Supply)

2 x 3000 A

Output Current at 0 to 15 Volt Direct Current (DC) Voltage

5000 A

Output Current at 0 to 15 Volt Direct Current (DC) Voltage (Dual Power Supply)

2 x 2500 A

Output Current at 0 to 24 Volt Direct Current (DC) Voltage

3000 A

Output Current at 0 to 30 Volt Direct Current (DC) Voltage

2500 A

Output Current at 0 to 48 Volt Direct Current (DC) Voltage

1500 A

Output Current at 0 to 60 Volt Direct Current (DC) Voltage

1250 A

Height

73 "

Weight

695 lbs

Footprint of Cabinet Width Including Busbars on the Rear Side

20 in

Footprint of Cabinet Depth Including Busbars on the Rear Side

24 in

Upgradable Output Power

If your future power requirements change, don't buy a new rectifier, simply add more power modules to your FlexKraft or reconfigure your existing FlexKraft to meet your updated requirements.

Serviceable

Simple design, easy accessibility, and self-diagnosing power modules makes the FlexKraft easy to trouble-shoot, service and repair.

Space-Saving

Compact design and capability to stack several units in one tower makes efficient use of shop floor space.

High Power Factor

>0.93 at rated load means no reative power penalty on your electricity bill and less strain on your local AC supply.

Ripple

Less than 2% of rated output current in the entire range of regulation. Typical value at nominal output current is less than 0.2%. This standard feature is perfect for ripple sensitive processes.

Modular Design

Any combination of power modules up to 120 VDC or 30,000 A can be supplied.

Options

*Analogue interface with four inputs and four outputs galvanically isolated. Control and status signals 0-10 VDC or 0/4-20 mA. *Analogue/Digital interface. Two controls, and two status signals 0-10 VDC and two controls and two status signals 24 VDC. *Digital interface with four inputs and four outputs. Control signals 24 VDC. Status signals via voltage free relay contacts; contact data 24 VDC or 24 VAC. Standard configuration: On/Off, Block/Run, Power On and Alarm. *Electrically controlled AC breaker. *External reference shunt, 60 mV. *Polarity Reversal. *Raise/Lower function. *Remote control options: ControlKraft Touch or ControlKraft Digital *RS-232C interface for control of one power supply. *Standard configuration: Iset, Uset, lact and Uact: 0-10 VDC. On/Off, Block/Run, Power On and Alarm as digital signals: 24 VDC. *Standard configuration: lset, Uset, lact and Uact: 4-20 mA

Manufacturer

KraftPowercon